Power supply

Approach to each client is individual:
- The client has a separate rack
- Due to the easily scalable power supply, each rack can supply the necessary power
- The client has the choice of level of fault tolerance from Tier3 to Tier4. In this case, not excluding the possibility of connecting by Tier2 also
Additional benefits include:
In the data center an increased level of energy is laid down. Allocated power can be several times larger than the standard supply of existing data centers up to 30 kW per rack
Power supply BEMOBILE includes:
- Two independent power supply route, consisting of 4 lines of 10 kV, each connected to different cells RP271 and TP560 powered from PS Cabelnaya, PS Kurenivskaya and PS Obolonskaya
- Two own transformer substation of 1.3 MW
- ATS system. Network-Network, Diesel Network
- Uninterruptible power supply system consisting of two UPS groups that are reserved by the scheme N+1, which allows a much higher level of fault tolerance, which guarantee an offline mode for at least 15 minutes
- Two groups of synchronized diesel generator produced by FG Wilson (UK). Diesel generators go on full power 2 minutes later after turning off the city power supply input lines and can provide an autonomous functioning of the whole data center
- Fault-tolerant power distribution system. Redundant power distribution system provides enhanced fault tolerance and high availability services
- The system of the main and emergency lighting, designed in accordance with SNIP and RB
The project incorporated the installation of two transformer substations with capacity of 2 MWt