Standards

  1. ANSI/TIA/EIA 942 (TIA 942) "Telecommunications Infrastructure Standard for Data Center" (2005 r.)
  2. Rules for Electrical Installation device (PUE)
  3. CH-512-78 (building standart) "Instructions for the building and room design for electronic computers" (edition of 2000 year)

TIER I

TIER II

TIERIII

TIER IV

ЦОД BEMOBILE

Energy input

One

One

One active and one reserved

Two active

Two active

Component reserving

N

N, N+1

N+1

2*(N+1)

N+1 - 2*(N+1)

Devision into autonomous units

No

No

No

Yes

Yes

Uninterrupted cooling

No

No

Possible

Yes

Yes

Hot change

No

No

Yes

Yes

Yes

Staff per duty

No

Min 1 engineer

Min 2 engineers

>2 engineers, 24х7

>2 engineers, 24х7

Load on the floor, kg/m2

600

800

1200

1200

1200

Service access

99,67%

99,75%

99,982%

99,995%

On client demand

Max time of dead time per year, h

28,8

22

1,6

0,4

On client demand

*Average power per rack, kWt

<2

<4

>6

>8

On client demand

*Max power per rack, kWt

<4

<8

>15

>20

> 25